Small wind / Buyer questions
Terminal blocks and crimp data
Does a bridge headline current rating cover every terminal-block combination?
The short answer
No universal transfer is justified. Phoenix Contact's RB 16-6 entry explicitly notes that jumper current values can differ with the modular terminal block used and refers to that terminal's accessory data. The bridge's identity and headline value therefore do not independently establish the supported current for every assembled combination.
Treat the combination as part of the rating condition
Identify the bridge, the terminal blocks it joins and the manufacturer's applicable accessory entry. A dimensional or pitch match addresses physical compatibility but does not supply the missing combined current statement. Keep the offered combination attached to the evidence instead of recording only the bridge's catalogue number. The manufacturer's qualification is part of the meaning of the current figure.
Review a retained bridge with changed terminals
In a hypothetical panel revision, the bridge part remains unchanged while the terminal-block selection changes. The supplier carries forward the previous accessory current conclusion using only the unchanged bridge reference. The reviewer requests the data applying to the revised combination. This does not establish that the revised capacity is lower or higher; it identifies the condition that the old statement has not demonstrated.
Preserve the applicable accessory assessment
Record the exact terminal and bridge references, the applicable terminal-specific accessory entry and the assessed demand. If a revised offer retains the bridge but changes the terminals, keep the revised combination assessment with the drawing revision. This gives the next reviewer a clear basis for comparing the assembled path. The example assigns no accepted bridge-terminal combination to MARSTON equipment.
Sources
Examples are illustrative. Confirm product-specific performance, compatibility and supply scope in the applicable documents.