Small wind / Buyer questions
Metering and instrument transformers
Can a shared busbar voltage transformer still represent a wind feeder after the bus is split?
The short answer
A busbar voltage transformer can represent several circuits only when the documented topology and measurement design support that use. Elexon's practice for certain large settlement circuits distinguishes a common unsplit bus from electrically separate sections. If a wind feeder and the voltage transformer are on different sections after a split, a voltage value can still be present without representing the feeder's intended measurement reference. Check the actual topology and meter inputs.
Identify the reference used in each bus arrangement
Record the single-line diagram, measurement point, bus sections, relevant switch states and the physical voltage reference for the meter. In a hypothetical operation a feeder remains on one section while the shared transformer remains on another after a split. A plausible voltage indication alone does not establish that it represents the feeder.
Compare topology and meter evidence during the event
Ask the qualified metering team which approved records identify the feeder's bus and the reference selected by its meter. Keep the evidence for each required operating arrangement. Distinguish this topology issue from secondary voltage drop or loss of a phase measurement. The published settlement example illustrates the boundary and the site design determines what applies.
Record which measurement states were verified
Have the responsible reviewer identify supported bus arrangements and any affected data intervals. Preserve the accepted drawings and test evidence with the wind import and export record. This gives a later reviewer a way to trace which voltage reference accompanied the feeder current, without assuming it stayed valid across every switchgear configuration.