Can a replacement wind cabinet power supply start all control modules if its continuous rating covers them?
The short answer
Continuous capacity is only one part of the decision. The new supply must also support the startup demands of the connected control modules under the intended restoration sequence. Ask for the expected startup current and output voltage behavior, especially when several loads begin together after an interruption.
Collect load-side startup information
List the connected controllers, relays, interface modules and other loads that depend on the supply. Record the ordinary operating draw and available startup current or input capacitance information separately. Omron explains that charging load-side capacitors can create a temporary demand that interacts with a switch-mode supply's overload behavior. Several such loads may prevent the expected output from being established.
Distinguish load-side startup current from the inrush that the power supply itself draws at its AC input. These values belong at different points in the electrical design.
Check the restoration state that matters
A routine restart of one module may succeed after the rest of the cabinet is already energized. A supply restoration can start multiple modules at once, depending on the approved control sequence. Ask how the supply handles a short overload, how output voltage recovers and what voltage the critical control loads need during initialization. A momentary reset may change the states available to the supervisory system.
Set the evidence for the quotation
Provide the load schedule and intended restoration sequence to the cabinet designer. Request the supply's applicable peak output or overload behavior, the load startup assumptions and the basis for any staged startup in the proposed design. The site acceptance plan should identify the relevant restoration state and record usable output voltage and equipment readiness evidence. Obtain the responsible designer's review before treating equivalent continuous wattage as proof of equivalent startup.
Sources